Application:
GMC series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current up to 95A, for making, breaking, frequently starting & controlling the AC motor. Combined with the auxiliary contact block, delay timer & machine-interlocking device etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter. With the thermal overload relay, it is combined into the electromagnetic starter. The Contactor is produced according to IEC60947-4.
Specification:
Type
|
AC1 duty
|
AC3 duty
|
Life time (x 104)
|
Aux.contact
|
200~240V
|
380~440V
|
500~550V
|
690V
|
Electrical
|
Mechanical
|
GMC-9
|
20A
|
2.5kW 11A
|
5kW 9A
|
4kW 7A
|
4kW 5A
|
250
|
2500
|
1NO1NC
|
GMC-12
|
20A
|
3.5kW 13A
|
5.5kW 12A
|
7.5kW 12A
|
7.5kW 9A
|
250
|
2500
|
GMC-18
|
25A
|
4.5kW 18A
|
7.5kW 18A
|
7.5kW 13A
|
7.5kW 9A
|
250
|
2500
|
GMC-22
|
32A
|
5.5kW 22A
|
11kW 22A
|
15kW 22A
|
15kW 18A
|
250
|
2500
|
GMC-32
|
50A
|
7.5kW 32A
|
15kW 32A
|
18.5kW 28A
|
18.5kW 21A
|
200
|
1500
|
2NO2NC
|
GMC-40
|
60A
|
11kW 40A
|
18.5kW 40A
|
22kW 32A
|
22kW 25A
|
200
|
1500
|
GMC-50
|
80A
|
15kW 55A
|
22kW 50A
|
30kW 43A
|
30kW 33A
|
200
|
1000
|
GMC-65
|
100A
|
18kW 65A
|
30kW 65A
|
37kW 60A
|
37kW 47A
|
200
|
1000
|
GMC-75
|
110A
|
22kW 75A
|
37kW 75A
|
45kW 64A
|
45kW 47A
|
200
|
1000
|
GMC-85
|
135A
|
25kW 85A
|
45kW 85A
|
45kW 75A
|
45kW 52A
|
200
|
1000
|