C65 series Miniature Circuit Breaker is applied to protect the over-current of electrical apparatus
and circuit device of the construction and similar building in the circuit of AC 50Hz or 60Hz, max rated voltage230V, max rated current 63A. Under normal condition, it may be also applied as the unfrequent make-breaker operation.
This product conform to IEC60898, GB10963 standard.
1. Model: C65 1pole D curve
2. Name of article: Mini Circuit Breaker
3. Voltage: 230V/400V
4. Frequency: 50Hz/60Hz
5. Ampere(A): 1A,2A,3A,4A,6A,10A, 16A, 20A, 25A, 32A,40A,50A,63A
6. Rated current (A): 6KA
7. Carton size: 22.2×7.8×8.5
8 Qty of package: 12PCS/Lot
9. Tripping curve: D
10. Weight of MCB: 0.1KG/PCS
Characteristics
Protection against both overload and short circuit
High short-circuit capacity
Its frame and parts adopt plastics of high fire-resistant and shockproof
Small apperance.light weight
Comply with the standard IEC60898 and GB10963
General
1. Application: For protecting cables and equipments against overload and short circuit.
2. General rules for choosing MCB:
a. Technical data of the network at the point considered:
The earthing systems short-circuit current at the circuit breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage.
B.There are 3curve characteristics for magnetic operation:
B curve (3-5In) protection and control of the circuits against length cables in TN and IT systems.
C curve (5-10 In) protection and control of the circuits against overloads and short-circuit; protection for resistive and inductive loads with low inrush current.
D curve (10-14 In) protection and control of the circuits against overloads and short-circuit; protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps).
Specification
Standard |
IEC/EN 60898-1
|
Electrical
features
|
Rated Current In
|
A
|
1,2,3,4,6,10,16,20,25,32,40,50,63
|
Poles
|
P
|
1,2,3,4
|
Rated Voltage Ue
|
V
|
230/400
|
Insulation Voltage Ui
|
V
|
500
|
Rated Frequency
|
Hz
|
50/60
|
Rated Breaking Capacity
|
A
|
3000,4500
|
Rated Impulse withstand Voltage(1.2/50)Uimp
|
V
|
4000
|
Dielectric Test Voltage at ind.Freq.for
1min
|
Kv
|
2
|
Pollution Degree
|
|
2
|
Thermo-magnetic Release Characteristic
|
|
B,C,D
|
Mechanical
features
|
Electrical Life
|
t
|
4000
|
Mechanical Life
|
t
|
10000
|
Protection Degree
|
|
IP20
|
Reference Temperature for Setting of
Thermal Element
|
°C
|
30
|
Ambient Temperature (with daily average
≤35°C)
|
°C
|
-5~+40(Special application please refer to temperature
compensation correction)
|
Storage Temperature
|
°C
|
-25~+70
|
Installation
|
Terminal Connection Type
|
|
Cable/Pin-type busbar
|
Terminal Size Top/Bottom for Cable
|
mm2
|
25
|
AWG
|
18-3
|
Terminal Size Top/Bottom for Busbar
|
mm2
|
25
|
AWG
|
18-3
|
Tightening Torque
|
N*m
|
2
|
In-lbs
|
18
|
Mounting
|
|
On DIN rail EN60715(35mm)by means of fast clip device
|
Connection
|
|
From top and bottom
|
Temperature Derating
Please refer to table below for temperature compensation correction
Rated Current In(A) |
Temperature compensation coefficient under various operational temperature
|
-10°C
|
0°C
|
10°C
|
20°C
|
30°C
|
40°C
|
50°C
|
55°C
|
60°C
|
1-6
|
1.20
|
1.14
|
1.09
|
1.05
|
1.00
|
0.96
|
0.80
|
0.75
|
0.70
|
10-32
|
1.18
|
1.12
|
1.08
|
1.04
|
1.00
|
0.96
|
0.92
|
0.88
|
0.84
|
40-60
|
1.16
|
1.12
|
1.07
|
1.03
|
1.00
|
0.97
|
0.87
|
0.83
|
0.80
|