Device short name
|
Compact INSX100N
|
Circuit breaker application
|
Distribution
|
Poles description
|
3P
|
Protected poles description
|
3t
|
Network type
|
AC
|
Network frequency
|
50/60 Hz
|
[In] rated current
|
100 A ( 40 °C )
|
[Ui] rated insulation voltage
|
800 V AC 50/60 Hz
|
[Uimp] rated impulse withstand voltage
|
8 kV
|
[Ue] rated operational voltage
|
690 V AC 50/60 Hz
|
Circuit breaker rating code
|
N
|
Breaking capacity
|
Icu 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
Icu 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Icu 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Icu 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 240 V AC 50/60 Hz conforming to NEMA AB1
50 kA at 480 V AC 50/60 Hz conforming to NEMA AB1
20 kA at 600 V AC 50/60 Hz conforming to NEMA AB1
85 kA at 240 V AC 50/60 Hz conforming to UL 508
50 kA at 480 V AC 50/60 Hz conforming to UL 508
20 kA at 600 V AC 50/60 Hz conforming to UL 508
|
[Ics] rated service breaking capacity
|
Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 35 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 36 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 90 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
|
Suitability for isolation
|
Yes conforming to IEC 60947-2
Yes conforming to EN 60947-2
|
Utilisation category
|
Category A
|
Trip unit name
|
TM-D
|
Trip unit technology
|
Thermal-magnetic
|
Trip unit rating
|
80 A ( 40 °C )
|
Protection type
|
Overload protection (thermal)
Short-circuit protection (magnetic)
|
Pollution degree
|
3 conforming to IEC 60947-1
|
Control type
|
Toggle
|
Mounting mode
|
Fixed
|
Mounting support
|
Backplate
|
Upside connection
|
Front
|
Downside connection
|
Front
|
Mechanical durability
|
50000 cycles
|
Electrical durability
|
50000 cycles 440 V In/2 conforming to IEC 60947-2
30000 cycles 440 V In conforming to IEC 60947-2
20000 cycles 690 V In/2 conforming to IEC 60947-2
10000 cycles 690 V In conforming to IEC 60947-2
|
Connection pitch
|
35 mm
|
Local signalling
|
Positive contact indication
|
Long time pick-up adjstment type Ir
|
Adjustable
|
Long time pick-up adjustment range
|
0.7...1 x In
|
Long time delay adjustment type
|
Fixed
|
[tr] long-time delay adjustment
|
15 s 6 x Ir
120...400 s 1.5 x In
|
Short-time pick-up adjustment type Isd
|
Fixed
|
[Isd] short-time pick-up adjustment range
|
640 A
|
Short-time delay adjustment type
|
Fixed
|
Height
|
161 mm
|
Width
|
105 mm
|
Depth
|
86 mm
|